Skip to content

1SDA067399R1 - XT1C 160 TMD 160-1600 3p F F

by ABB
Original price $181.46 - Original price $181.46
Original price
$181.46
$181.46 - $181.46
Current price $181.46

C.BREAKER TMAX XT1C 160 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 160-1600 A



ABB EcoSolutions
Item Value
ABB EcoSolutions Yes

Circular Value
Item Value
Circular Design Principles Recyclability Rate Design for Closing Resource Loops - Standard EN45555 - 60.9 %
Conflict Minerals Reporting Template (CMRT) 9AKK108467A5658
End of Life Instructions 9AKK108468A2347
Group Waste to Landfill Target UL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA 9AKK108467A8326

Eco Transparency
Item Value
Environmental Product Declaration - EPD 9AKK108468A1890

Environmental
Item Value
Environmental Information 9AKK107991A8215 9AKK108467A6707
REACH Declaration 9AKK108466A1425
RoHS Information 9AKK108466A1424
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP 0d8bc7a2-0b2f-4c4e-b0d2-ae3184d07c12 Italy (IT)
Simplified SCIP ab107f86-ac30-4f6a-a6bf-c4d8c77a0fd2 France (FR)4ce86c8a-88a3-4668-b9fe-6d159b3b770c Poland (PL)2b6d4e8f-9999-4183-a923-afbb4bdcec78 Finland (FI)1b141b21-8bef-4f72-8f3e-ddd51c5ec259 Norway (NO)974eeae4-e997-42f0-aa0d-58883071678c Netherlands (NL)c0df14b2-ce11-4e19-a2d5-72e2790aa9cc Netherlands (NL)b756e454-2ef3-4dc7-99e0-091b44577511 Germany (DE)99c1470b-f1a5-48b0-8949-840c4be74894 Denmark (DK)e16d074d-620a-4ea1-8227-b05dc2e7d098 Germany (DE)dfb95055-9cf7-4ec6-b0e7-801c62ca7cc8 Croatia (HR)9fc57840-b252-4713-8387-c3b5c39c2768 Czech Republic (CZ)56162500-c94b-403f-a284-3e358af29456 Netherlands (NL)82077ecd-9e46-4ba5-85c7-22fd9245ee2d Netherlands (NL)df47e79a-6de1-4aa8-83e4-3b4ebc60686b Estonia (EE)91ca0d03-e2ae-40be-88e0-e06a7b181f24 Greece (GR)21de00c2-cdbb-4cc5-a139-d1e3d26dffcb Portugal (PT)91902059-0a7b-46c8-9eda-6bb7beb04a2b Bulgaria (BG)83cedd21-6566-49aa-bd8f-fa5be6b586dd Sweden (SE)4f0c602c-433f-4412-8704-722fe1de2a92 Poland (PL)1b963a22-3a58-43d0-94c5-819ab7622567 France (FR)5489a759-29a8-46b8-a5c0-42d61d45ed5d Sweden (SE)b8e985c9-c29a-4e6d-a0f0-f79c981441a9 Germany (DE)0a6e7309-6bb1-4725-9934-8c06601b79c0 Germany (DE)3daf304a-39bc-447c-a8cd-0e009652dae7 Spain (ES)4a0eb37f-875b-48f5-ad3a-e2fe91f042c6 Netherlands (NL)c8b2a3ef-2fdc-48b9-9068-d7b46a9d3213 Poland (PL)

Ordering
Item Value
Order Code US and Canada XT1CE3160AFF000XXX
E-Number (Finland) 3638779
Minimum Order Quantity 1 piece
Customs Tariff Number 85362090

Dimensions
Item Value
Product Net Width 76.2 mm
Product Net Height 130 mm
Product Net Depth / Length 70 mm
Product Net Weight 1.1 kg

Additional Information
Item Value
Circuit Breaker Type to be Associated Power Distribution
Connecting Capacity Main Circuit Busbar 45.5 ... 80 mm²
Current Type AC/DC
Electrical Durability 120 cycles per hour8000 cycle
Mechanical Durability 240 cycles per hour25000 cycle
Number of Poles 3
Opening Time CB with SOR 15 msCB with UVR 15 ms
Order Multiple 1 piece
Power Loss at Rated Operating Conditions per Pole 15 W
Product Main Type SACE Tmax XT
Product Name Moulded Case Circuit Breaker
Product Type Automatic Circuit Breaker
Rated Current (In) 160 A
Rated Frequency (f) 50 / 60 Hz
Rated Voltage (Ur) 690 V
Rated Impulse Withstand Voltage (Uimp) 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii) 1600 A
Rated Insulation Voltage (Ui) 800 V
Rated Operational Voltage 690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics) (220 V AC) 40 kA(230 V AC) 40 kA(240 V AC) 40 kA(380 V AC) 25 kA(415 V AC) 25 kA(440 V AC) 12.5 kA(500 V AC) 9 kA(525 V AC) 8 kA(690 V AC) 4 kA(250 V DC) 2 Poles in Series 25 kA(500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu) (220 V AC) 40 kA(230 V AC) 40 kA(240 V AC) 40 kA(380 V AC) 25 kA(415 V AC) 25 kA(440 V AC) 25 kA(500 V AC) 18 kA(525 V AC) 8 kA(690 V AC) 4 kA(250 V DC) 2 Poles in Series 25 kA(500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu) 160 A
Recommended Screw Driver Main Circuit M6
Release TMD
Release Type TM
RoHS Date NA
Setting Range 112...160 A
Short-Circuit Performance Level C
Standards IEC
Sub-type XT1
Terminal Connection Type Front
Terminal Type Bolt
Tightening Torque 6 N·m
Version F
CAD Dimensional Drawing 1SDH001295R0008

Classifications
Item Value
ETIM 9 EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code Q
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
eClass V11.1 : 27370409

No Links Available.