SIRIUS MOTOR STARTER M200D AS-I COMMUNICATION: AS-INTERFACE REVERSING STARTER BASIC MECHANICALLY SWITCHING 3 400V AC/5.5KW; 1.5A...12.00A; ELECTRONIC OVERLOAD PROTECTION; THERMISTOR: THERMOCLICK / PTC WITH BRAKE CONTACT 400V AC 2DI AS-I + 2DI / 1DO ON DEVICE HAN Q4/2 - HAN Q8/0



Specifications
Item Value
Depth 159 mm
Country of Origin DE
Width 294 mm
Height 215 mm
With fuse true
Release class CLASS 10
With transformer false
External reset possible true
Rail mounting possible false
Number of command positions 2
Number of indicator lights 12
Voltage type for actuating DC
Degree of protection (IP) IP65
Degree of protection (NEMA) 12
Rated operation current Ie 12 A
With short-circuit release true
Supporting protocol for ASI true
Suitable for emergency stop false
Supporting protocol for CAN false
Supporting protocol for LON false
Supporting protocol for MODBUS false
Supporting protocol for SERCOS false
Supporting protocol for TCP/IP false
Overload release current setting 1.5 A
Supporting protocol for SUCONET false
Supporting protocol for INTERBUS false
Supporting protocol for PROFIBUS false
Kind of motor starter Reversing starter
Supporting protocol for DeviceNet false
Supporting protocol for PROFIsafe false
Rated power, 460 V, 60 Hz, 3-phase 5.5 kW
Supporting protocol for EtherNet/IP false
Supporting protocol for PROFINET IO false
Supporting protocol for SafetyBUS p false
Rated operation current at AC-3, 400 V 12 A
Rated operation power at AC-3, 400 V 5.5 kW
Supporting protocol for Data-Highway false
Supporting protocol for PROFINET CBA false
Rated control supply voltage Us at DC 20.4 V
Supporting protocol for INTERBUS-Safety false
Supporting protocol for DeviceNet Safety false
Supporting protocol for other bus systems false
Temperature compensated overload protection true
Rated operation power at AC-3, 230 V, 3-phase 3 kW
Supporting protocol for Foundation Fieldbus false
Type of electrical connection of main circuit Other
Ambient temperature, upper operating limit 40 °C
Coordination class according to IEC 60947-4-3 Class 1
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as normally closed contact 0
Supporting protocol for AS-Interface Safety at Work false
Rated conditional short-circuit current, type 2, 230 V 50000 A
Rated conditional short-circuit current, type 2, 400 V 50000 A
Rated conditional short-circuit current, type 1, 480 Y/277 V 50000 A
Type of electrical connection for auxiliary- and control current circuit Other