1SBL419025R8711 - GAE75-10-11 125V DC Contactor

by ABB
Original price $492.66 - Original price $492.66
Original price
$492.66
$492.66 - $492.66
Current price $492.66

GAE75 contactors are designed for DC circuit switching. Arc suppression is more difficult in DC than in AC. To choose a contactor, it is necessary to know the current and voltage to be broken as well as the L/R time constant of the power circuit to be controlled. GAE 75 contactors are of the block type design. - Main poles: the contactors are fitted with arc chutes with permanent magnets specially designed for DC breaking. The three contactor paths are arranged in series via two supplied and fitted insulated connections (25 mm²). The GAE75 are "single-pole" devices for which the connection polarities indicated next to the connection terminals must be respected. Furthermore, they are marked 1L1 for the positive terminal and 2T1 for the negative terminal. - Auxiliary contact: 1 CAL 5-11 side-mounted add-on auxiliary contact block (GAE75-10-11 types) - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding) - Accessories: a wide range of accessories is available



Ordering
Item Value
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900

Dimensions
Item Value
Product Net Width 94 mm
Product Net Depth / Length 108 mm
Product Net Height 132 mm
Product Net Weight 1.3 kg

Technical
Item Value
Number of Main Contacts NO 3
Number of Main Contacts NC 0
Number of Auxiliary Contacts NO 1
Number of Auxiliary Contacts NC 1
Rated Operational Voltage Auxiliary Circuit 690 VMain Circuit 1000 V DC
Rated Frequency (f) Auxiliary Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith) acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 125 Aacc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-15 (Ie) (500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(380 / 400 V) 3 A
Short-Circuit Protective Devices Auxiliary Circuit - gG Type Fuses 10 AgG Type Fuses 160 A
Rated Short-time Withstand Current Low Voltage (Icw) for 0.1 s 140 Afor 1 s 100 A
Maximum Electrical Switching Frequency 300 cycles per hour
Rated Operational Current DC-1 (Ie) (1000 V) 1-Pole, 40 °C 35 A(1000 V) 1-Pole, 55 °C 35 A(1000 V) 1 Pole, 70 °C 35 A(110 V) 1-Pole, 40 °C 120 A(110 V) 1-Pole, 55 °C 100 A(110 V) 1-Pole, 70 °C 85 A(220 V) 1-Pole, 40 °C 120 A(220 V) 1-Pole, 55 °C 100 A(220 V) 1-Pole, 70 °C 85 A(440 V) 1-Pole, 40 °C 100 A(440 V) 1-Pole, 55 °C 100 A(440 V) 1-Pole, 70 °C 85 A(600 V) 1-Pole, 40 °C 75 A(600 V) 1-Pole, 55 °C 75 A(600 V) 1-Pole, 70 °C 75 A(72 V) 1-Pole, 40 °C 120 A(72 V) 1-Pole, 55 °C 100 A(72 V) 1-Pole, 70 °C 85 A
Rated Operational Current DC-3 (Ie) (110 V) 1-Pole, 40 °C 120 A(110 V) 1-Pole, 55 °C 100 A(220 V) 1-Pole, 40 °C 100 A(220 V) 1-Pole, 55 °C 100 A(440 V) 1-Pole, 40 °C 85 A(440 V) 1-Pole, 55 °C 85 A(72 V) 1-Pole, 40 °C 120 A(72 V) 1-Pole, 55 °C 100 A
Rated Operational Current DC-5 (Ie) (110 V) 1-Pole, 40 °C 85 A(110 V) 1-Pole, 55 °C 85 A(220 V) 1-Pole, 40 °C 85 A(220 V) 1-Pole, 55 °C 85 A(440 V) 1-Pole, 40 °C 35 A(440 V) 1-Pole, 55 °C 35 A(72 V) 1-Pole, 40 °C 85 A(72 V) 1-Pole, 55 °C 85 A
Rated Operational Current DC-13 (Ie) (24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.30 A / 66 W(250 V) 0.3 / 75 W
Rated Insulation Voltage (Ui) acc. to IEC 60947-4-1 1000 Vacc. to IEC 60947-5-1 690 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp) 8 kV
Mechanical Durability 5 million
Maximum Mechanical Switching Frequency 3600 cycles per hour
Rated Control Circuit Voltage (Uc) DC Operation 125 V
Coil Consumption Average Holding Value, from Warm State 4 WAverage Pull-in Value, from Cold State 200 WHolding at Max. Rated Control Circuit Voltage 50 Hz 4 WHolding at Max. Rated Control Circuit Voltage DC 4 WPull-in at Max. Rated Control Circuit Voltage DC 200 V·A
Operate Time Between Coil De-energization and NC Contact Closing 8 ... 18 msBetween Coil De-energization and NO Contact Opening 5 ... 15 msBetween Coil Energization and NC Contact Opening 10 ... 27 msBetween Coil Energization and NO Contact Closing 30 ... 30 ms
Mounting on DIN Rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH75-25 (75 x 25 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied) 2 x M6 screws placed diagonally
Connecting Capacity Main Circuit Flexible with Cable End 6 ... 16 mm²Rigid Cable 6 ... 25 mm²
Connecting Capacity Auxiliary Circuit Flexible with Cable End 0.75 ... 2.5 mm²Rigid Cable 1 ... 4 mm²
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Connecting Terminals (delivered in open position) Main Poles M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector
Terminal Type Screw Terminals

Technical UL/CSA
Item Value
Maximum Operating Voltage UL/CSA Main Circuit 1000 V DC
General Use Rating UL/CSA (1000 V DC) 35 A(440 V DC) 100 A(600 V DC) 75 A

Environmental
Item Value
Ambient Air Temperature Close to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °CNear Contactor for Operation in Free Air (Uc) -40 ... 70 °C
Climatic Withstand acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible Without Derating 3000 m
RoHS Status Following EU Directive 2011/65/EU

Classifications
Item Value
Object Classification Code Q
ETIM 4 EC002552 - Power contactor, DC switching
ETIM 5 EC002552 - Power contactor, DC switching
eClass V11.0 : 27371018