Skip to content

1SCA104857R1001 - OT25F3 SWITCH-DISCONNECTOR

by ABB
Original price $14.51 - Original price $14.51
Original price
$14.51
$14.51 - $14.51
Current price $14.51

3-pole, front operated, base mounted, DIN-rail mountable switch-diconnector / non-fusible diconnect switch with protected clamp terminals, handle and shaft are not included



Circular Value
Item Value
Conflict Minerals Reporting Template (CMRT) 9AKK108467A5658
Environmental Information 1SCC301262D0201
REACH Declaration 1SCC011021D0201
RoHS Information 1SCC011020D0201

Ordering
Item Value
Minimum Order Quantity 10 piece
Customs Tariff Number 85365080
Country of Origin Finland (FI)

Dimensions
Item Value
Product Net Width 35 mm
Product Net Height 68 mm
Product Net Depth / Length 56 mm
Product Net Weight 0.09 kg

Technical
Item Value
Rated Operational Current AC-21A (Ie) (380 ... 415 V) 25 A(500 V) 25 A(690 V) 25 A
Rated Operational Current AC-22A (Ie) (380 ... 415 V) 25 A(500 V) 25 A(690 V) 25 A
Rated Operational Current AC-23A (Ie) (380 ... 415 V) 20 A(500 V) 20 A(690 V) 11 A
Rated Operational Power AC-23A (Pe) (220 ... 240 V) 4 kW(400 ... 415 V) 9 kW(500 V) 9 kW(690 V) 9 kW
Conventional Free-air Thermal Current (Ith) Θ = 40 °C 32 A
Conventional Thermal Current (Ithe) Fully Enclosed 32 A
Rated Impulse Withstand Voltage (Uimp) 8 kV
Rated Insulation Voltage (Ui) acc. to IEC/EN 60664-1 750 V
Rated Operational Voltage Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm) (690 V) 0.71 kA
Rated Short-time Withstand Current Low Voltage (Icw) for 1 s 0.5 kA
Rated Conditional Short-Circuit Current (Inc) (40 A fuse, ≤415V) 50 kA(25 A fuse, 690 V) 50 kA
Power Loss at Rated Operating Conditions per Pole 0.6 W
Pollution Degree 3
Handle Type KnobHandle and shaft not included
Switches Operating Mechanism Mechanism on Top of the Switch
Distance Between Phases Standard
Position of Line Terminals Top In - Bottom OutBottom In - Top Out
Operating Mode Front operated
Standards IEC 60947-3 / UL 508 / CSA C22.2 No. 14
Special Functions No
Mounting Type Base mounting
Number of Poles 3
Cable Cross-Section Cu 0.75 ... 10 mm²
Wire Stripping Length Main Circuit 9-10 mmMain Circuit 0.35-0.38 in
Degree of Protection Front IP20
Terminal Type Screw Terminals
Tightening Torque acc. IEC 60947-1 0.8 N·m
Mechanical Durability 20000
Lock Type No

Technical UL/CSA
Item Value
Maximum Operating Voltage UL/CSA 600 V
Ampere Rating 30 A
Horsepower Rating UL/CSA (110 ... 120 V AC) Single Phase 1.5 Hp(240 V AC) Single Phase 3 Hp(440 ... 480 V AC) Single Phase 7.5 Hp(550 ... 600 V AC) Single Phase 10 Hp(220 ... 240 V AC) Three Phase 7,5 Hp(440 ... 480 V AC) Three Phase 15 Hp(550 ... 600 V AC) Three Phase 20 Hp
Wire Stripping Length Main Circuit 9-10 mmMain Circuit 0.35-0.38 in
Tightening Torque acc. IEC 60947-1 0.8 N·m
Tightening Torque UL/CSA 7 in·lb

Environmental
Item Value
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Environmental Information 1SCC301262D0201

Classifications
Item Value
Object Classification Code Q
ETIM 9 EC000216 - Switch disconnector (low voltage)
IDEA Granular Category Code (IGCC) 5290 >> Disconnect switch
eClass V11.1 : 27371403
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland) 3601428
E-Number (Sweden) 3170938