The AF146-30-11B-11 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 75 kW / 400 V AC (AC-3) or 100 hp / 480 V UL and switching power circuits up to 225 A (AC-1) or 200 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Technical
Item |
Value |
Number of Main Contacts NO |
3 |
Number of Main Contacts NC |
0 |
Number of Auxiliary Contacts NO |
1 |
Number of Auxiliary Contacts NC |
1 |
Rated Operational Voltage |
Main Circuit 1000 V |
Rated Frequency (f) |
Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith) |
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 225 A |
Rated Operational Current AC-1 (Ie) |
(1000 V) 40 °C 225 A(1000 V) 55 °C 200 A(1000 V) 60 °C 200 A(1000 V) 70 °C 175 A(690 V) 40 °C 225 A(690 V) 55 °C 200 A(690 V) 60 °C 200 A(690 V) 70 °C 175 A |
Rated Operational Current AC-3 (Ie) |
(415 V) 55 °C 146 A(440 V) 55 °C 146 A(500 V) 55 °C 130 A(690 V) 55 °C 93 A(1000 V) 55 °C 60 A(380 / 400 V) 55 °C 146 A(220 / 230 / 240 V) 55 °C 146 |
Rated Operational Current AC-3e (Ie) |
(415 V) 60 °C 146 A(440 V) 60 °C 146 A(500 V) 60 °C 130 A(690 V) 60 °C 93 A(1000 V) 60 °C 54 A(380 / 400 V) 60 °C 146 A(220 / 230 / 240 V) 60 °C 146 A |
Rated Operational Power AC-3 (Pe) |
(415 V) 75 kW(440 V) 90 kW(500 V) 90 kW(690 V) 90 kW(1000 V) 75 kW(380 / 400 V) 75 kW(220 / 230 / 240 V) 45 kW |
Rated Operational Power AC-3e (Pe) |
(415 V) 75 kW(440 V) 90 kW(500 V) 90 kW(690 V) 90 kW(1000 V) 75 kW(380 / 400 V) 75 kW(220 / 230 / 240 V) 45 kW |
Rated Breaking Capacity AC-3 |
8 x Ie AC-3 |
Rated Breaking Capacity AC-3e |
8.5 x Ie AC-3e |
Rated Making Capacity AC-3 |
10 x Ie AC-3 |
Rated Making Capacity AC-3e |
12 x Ie AC-3e |
Short-Circuit Protective Devices |
gG Type Fuses 315 A |
Rated Short-time Withstand Current Low Voltage (Icw) |
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A |
Maximum Breaking Capacity |
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A |
Maximum Electrical Switching Frequency |
(AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour |
Rated Insulation Voltage (Ui) |
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V |
Rated Impulse Withstand Voltage (Uimp) |
Main Circuit 8 kV |
Mechanical Durability |
5 million |
Maximum Mechanical Switching Frequency |
300 cycles per hour |
Coil Operating Limits |
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
Rated Control Circuit Voltage (Uc) |
50 Hz 24 ... 60 V60 Hz 24 ... 60 VDC Operation 20 ... 60 V |
Coil Consumption |
Holding at Max. Rated Control Circuit Voltage 50 Hz 5.5 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 5.5 V·AHolding at Max. Rated Control Circuit Voltage DC 2.5 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 225 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 225 V·APull-in at Max. Rated Control Circuit Voltage DC 210 W |
Operate Time |
Between Coil De-energization and NO Contact Opening 37 ... 47 msBetween Coil Energization and NO Contact Closing 25 ... 55 ms |
Connecting Capacity Main Circuit |
Flexible 2 x 10 ... 70 mm²Rigid Cu-Cable 2 x 10 ... 95 mm² |
Connecting Capacity Auxiliary Circuit |
Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm² |
Degree of Protection |
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
Terminal Type |
Main Circuit: Bars |