1SFL497025R6911 - GAF185-10-11 48-130V 50/60Hz / 48-130V DC Contactor

by ABB
Original price $1,072.07 - Original price $1,072.07
Original price
$1,072.07
$1,072.07 - $1,072.07
Current price $1,072.07

A 3-pole Contactor suitable for DC-1 applications where all three poles must be connected in series in a 1-pole configuration up to max 1000 VDC. Operated with wide control voltage range 48-130 V, AC/DC



Ordering
Item Value
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900

Dimensions
Item Value
Product Net Width 111.5 mm
Product Net Depth / Length 160 mm
Product Net Height 196 mm
Product Net Weight 3 kg

Technical
Item Value
Number of Main Contacts NO 1
Number of Main Contacts NC 0
Number of Auxiliary Contacts NO 1
Number of Auxiliary Contacts NC 1
Rated Operational Voltage Main Circuit 1000 V
Conventional Free-air Thermal Current (Ith) acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A
Rated Operational Current DC-1 (Ie) (1000 V) 3 Poles in Series, 40 °C 275 A(1000 V) 3 Poles in Series, 55 °C 250 A(1000 V) 3 Poles in Series, 70 °C 180 A(220 V) 3 Poles in Series, 40 °C 275 A(220 V) 3 Poles in Series, 55 °C 250 A(220 V) 3 Poles in Series, 70 °C 180 A(400 V) 3 Poles in Series, 40 °C 275 A(400 V) 3 Poles in Series, 55 °C 250 A(400 V) 3 Poles in Series, 70 °C 180 A(600 V) 3 Poles in Series, 40 °C 275 A(600 V) 3 Poles in Series, 55 °C 250 A(600 V) 3 Poles in Series, 70 °C 180 A
Rated Insulation Voltage (Ui) acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp) Main Circuit 8 kV
Mechanical Durability 5 million
Maximum Mechanical Switching Frequency 300 cycles per hour
Coil Operating Limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc) 50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
Coil Consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage DC 2 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 430 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 430 V·APull-in at Max. Rated Control Circuit Voltage DC 500 V·A
Connecting Capacity Main Circuit Bar 24 mm²Rigid Al-Cable 25 ... 150 mm²Rigid Cu-Cable 6 ... 185 mm²
Connecting Capacity Auxiliary Circuit Flexible with Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type Main Circuit: Bars

Technical UL/CSA
Item Value
Maximum Operating Voltage UL/CSA Main Circuit 600 V
General Use Rating UL/CSA (1000 V DC) 250 A(440 V DC) 250 A(600 V DC) 250 A

Environmental
Item Value
Ambient Air Temperature Operation -40 ... +80 °CStorage -40 ... +70 °C
Maximum Operating Altitude Permissible Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27 Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Classifications
Item Value
Object Classification Code Q
ETIM 4 EC002552 - Power contactor, DC switching
ETIM 5 EC002552 - Power contactor, DC switching
eClass V11.0 : 27371018
IDEA Granular Category Code (IGCC) 4763 >> Power contactor, DC switching

No Links Available.