Skip to content

1SDA072368R1 - E2.2H 1600 Ekip Hi-Touch LSI 3p WMP

by ABB
Original price $7,362.81 - Original price $7,362.81
Original price
$7,362.81
$7,362.81 - $7,362.81
Current price $7,362.81

MOVING PART FOR C.BREAKER SACE EMAX2 E2.2H 1600 THREE-POLE WITH SOLID-STATE RELEASE IN AC EKIP/HI-TOUCH-LSI R 1600 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED



ABB EcoSolutions
Item Value
ABB EcoSolutions Yes

Circular Value
Item Value
Circular Design Principles Recyclability Rate Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Conflict Minerals Reporting Template (CMRT) 9AKK108467A5658
End of Life Instructions 9AKK108468A2361
Group Waste to Landfill Target UL 2799 Zero Waste To Landfill Validation available

Eco Transparency
Item Value
Environmental Product Declaration - EPD 9AKK108468A1902 9AKK108468A1909

Environmental
Item Value
Environmental Information 9AKK10103A1038 9AKK108467A6707
REACH Declaration 9AKK108466A1425
RoHS Information 9AKK108466A1424
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP 5db9272f-d385-4a4a-a0e6-73274e7613b2 Italy (IT)

Ordering
Item Value
Order Code US and Canada Z2HSEJAJ200A000000XX
Minimum Order Quantity 1 piece
Customs Tariff Number 85362090

Dimensions
Item Value
Product Net Width 317 mm
Product Net Height 425 mm
Product Net Depth / Length 383 mm
Product Net Weight 48 kg

Additional Information
Item Value
Current Type AC
Electrical Durability Ue =< 440 V 12000 cycleUe = 500 ... 690 V 10000 cycle30 cycles per hour
Mechanical Durability 25000 cycle60 cycles per hour
Number of Poles 3
Power Loss 288 W
Product Main Type SACE Emax 2
Product Name Air Circuit Breaker
Product Type Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) 100 %
Rated Current (In) 1600 A
Rated Voltage (Ur) 690 V
Rated Impulse Withstand Voltage (Uimp) acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui) AC 1000 V
Rated Operational Voltage 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics) (220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(660 V AC) 85 kA(690 V AC) 85 kA
Rated Short-time Withstand Current Low Voltage (Icw) for 1 s 85 kAfor 3 s 66 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu) (400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 85 kA(525 V AC) 85 kA(690 V AC) 85 kA
Rated Uninterrupted Current (Iu) 1600 A
Release Ekip Hi-Touch LSI
Release Type EL
Short-Circuit Performance Level H
Standards IEC
Sub-type E2.2
Version W
CAD Dimensional Drawing 1SDH001252R0431

Classifications
Item Value
IDEA Granular Category Code (IGCC) 4926 >> Air circuit breakers
Object Classification Code Q
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
eClass V11.1 : 27370409

No Links Available.