GAE75 contactors are designed for DC circuit switching. Arc suppression is more difficult in DC than in AC. To choose a contactor, it is necessary to know the current and voltage to be broken as well as the L/R time constant of the power circuit to be controlled. GAE 75 contactors are of the block type design. - Main poles: the contactors are fitted with arc chutes with permanent magnets specially designed for DC breaking. The three contactor paths are arranged in series via two supplied and fitted insulated connections (25 mm²). The GAE75 are "single-pole" devices for which the connection polarities indicated next to the connection terminals must be respected. Furthermore, they are marked 1L1 for the positive terminal and 2T1 for the negative terminal. - Control circuit: DC operated with standard double-winding DC coils (with add-on factory-mounted lagging contact for insertion of the"holding" winding) - Accessories: a wide range of accessories is available
Technical
Item |
Value |
Number of Main Contacts NO |
3 |
Number of Main Contacts NC |
0 |
Number of Auxiliary Contacts NO |
0 |
Number of Auxiliary Contacts NC |
0 |
Rated Operational Voltage |
Auxiliary Circuit 690 VMain Circuit 1000 V DC |
Conventional Free-air Thermal Current (Ith) |
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 125 A |
Short-Circuit Protective Devices |
gG Type Fuses 160 A |
Rated Short-time Withstand Current Low Voltage (Icw) |
for 0.1 s 140 Afor 1 s 100 A |
Maximum Electrical Switching Frequency |
300 cycles per hour |
Rated Operational Current DC-1 (Ie) |
(1000 V) 1-Pole, 40 °C 35 A(1000 V) 1-Pole, 55 °C 35 A(1000 V) 1 Pole, 70 °C 35 A(110 V) 1-Pole, 40 °C 120 A(110 V) 1-Pole, 55 °C 100 A(110 V) 1-Pole, 70 °C 85 A(220 V) 1-Pole, 40 °C 120 A(220 V) 1-Pole, 55 °C 100 A(220 V) 1-Pole, 70 °C 85 A(440 V) 1-Pole, 40 °C 100 A(440 V) 1-Pole, 55 °C 100 A(440 V) 1-Pole, 70 °C 85 A(600 V) 1-Pole, 40 °C 75 A(600 V) 1-Pole, 55 °C 75 A(600 V) 1-Pole, 70 °C 75 A(72 V) 1-Pole, 40 °C 120 A(72 V) 1-Pole, 55 °C 100 A(72 V) 1-Pole, 70 °C 85 A |
Rated Operational Current DC-3 (Ie) |
(110 V) 1-Pole, 40 °C 120 A(110 V) 1-Pole, 55 °C 100 A(220 V) 1-Pole, 40 °C 100 A(220 V) 1-Pole, 55 °C 100 A(440 V) 1-Pole, 40 °C 85 A(440 V) 1-Pole, 55 °C 85 A(72 V) 1-Pole, 40 °C 120 A(72 V) 1-Pole, 55 °C 100 A |
Rated Operational Current DC-5 (Ie) |
(110 V) 1-Pole, 40 °C 85 A(110 V) 1-Pole, 55 °C 85 A(220 V) 1-Pole, 40 °C 85 A(220 V) 1-Pole, 55 °C 85 A(440 V) 1-Pole, 40 °C 35 A(440 V) 1-Pole, 55 °C 35 A(72 V) 1-Pole, 40 °C 85 A(72 V) 1-Pole, 55 °C 85 A |
Rated Insulation Voltage (Ui) |
acc. to IEC 60947-4-1 1000 Vacc. to IEC 60947-5-1 690 Vacc. to UL/CSA 600 V |
Rated Impulse Withstand Voltage (Uimp) |
8 kV |
Maximum Mechanical Switching Frequency |
3600 cycles per hour |
Rated Control Circuit Voltage (Uc) |
DC Operation 110 V |
Coil Consumption |
Average Holding Value, from Warm State 4 WAverage Pull-in Value, from Cold State 200 WHolding at Max. Rated Control Circuit Voltage 50 Hz 4 WHolding at Max. Rated Control Circuit Voltage DC 4 WPull-in at Max. Rated Control Circuit Voltage DC 200 V·A |
Operate Time |
Between Coil De-energization and NO Contact Opening 5 ... 15 msBetween Coil Energization and NO Contact Closing 30 ... 30 ms |
Mounting on DIN Rail |
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH75-25 (75 x 25 mm Mounting Rail) acc. to IEC 60715 |
Mounting by Screws (not supplied) |
2 x M6 screws placed diagonally |
Connecting Capacity Main Circuit |
Flexible with Cable End 6 ... 16 mm²Rigid Cable 6 ... 25 mm² |
Connecting Capacity Auxiliary Circuit |
Flexible with Cable End 0.75 ... 2.5 mm²Rigid Cable 1 ... 4 mm² |
Degree of Protection |
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
Connecting Terminals (delivered in open position) Main Poles |
M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector |
Terminal Type |
Screw Terminals |