The softstarter PSE72-600-70 has a rated maximum operational current of 72 A with an operating voltage span from 208...600 V AC. The rated control voltage is between 100...250 V AC at 50/60 Hz. PSE features a two-phase control with a soft start and stop through a voltage or a torque ramp. It has built-in bypass for easy installation and energy saving. A RUN, TOR, and Event signal is available from a relay output in NO (normally open state). The PSE has functions such as current limit, kickstart, analog output, EOL, underload, and locked rotor protection. To interact with PSE, it has an Illuminated display that uses symbols to become language neutral. As an option, you can add an identical external keypad with a rating of IP66. There are three ways to communicate with PSE. It can be done by hardwire inputs Start/Stop or by Reset of fault. Another popular option is the built-in fieldbus communication Modbus RTU. You can also use an external adaptor and a Fieldbus plug. PSE is a true general purpose softstarter. It’s a perfect balance between high starting capacity and cost efficiency. Very suitable for small to medium-sized three-phase motors with nominal currents from 18...370 A. Typical applications are, for example, pumps, fans, compressors, and conveyors.
Technical
Item |
Value |
Rated Operational Voltage |
208 ... 600 V AC |
Rated Control Supply Voltage (Us) |
100 ... 250 V AC |
Rated Control Circuit Voltage (Uc) |
24 V DC |
Rated Frequency (f) |
50/60 HzMain Circuit 50 / 60 Hz |
Rated Operational Power - In-Line Connection (Pe) |
(230 V) 18.5 kW(400 V) 37 kW(500 V) 45 kW |
Rated Operational Current - In-Line Connection (Ie) |
72 A |
Service Factor Percentage |
100 % |
Overload Protection |
Build-in electronic overload protection |
Integrated Electronic Overload |
Yes |
Adjustable Rated Motor Current Ie |
30 ... 100 % |
Starting Capacity at Maximum Rated Current Ie |
4xIe for 10s |
Ramp Time |
0 ... 30 second [unit of time]1 ... 30 second [unit of time] |
Initial Voltage During Start |
30 ... 70 % |
Step Down Voltage Special Ramp |
No % |
Current Limit Function |
1.5 ... 7xIe |
Switch for Inside Delta Connection |
No |
Run Signal Relay |
Yes |
By-pass Signal Relay |
Yes |
Fault Signal Relay |
Yes |
Overload Signal Relay |
Yes |
Analog Outputs |
4…20 mA |
Signal Indication Completed Start Ramp (LED) |
Green |
Signal Indication Ready to Start/Standby ON (LED) |
Green |
Signal Indication Running R (LED) |
Green |
Signal Indication Ramping Up/Down (LED) |
Green |
Signal Indication Protection (LED) |
Yellow |
Signal Indication Fault (LED) |
Red |
Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time |
10 |
Communication |
Modbus-RTU |
Degree of Protection |
IP00 |
Terminal Type |
Screw Terminals |
Connecting Capacity Main Circuit |
Hole Diameter 8.5 mmRigid 1/2 x 2.5 ... 70 mm²Width and Thickness 17.5x5 mm |
Connecting Capacity Control Circuit |
Rigid 1 x 2.5 mm²Rigid 2 x 1.5 mm² |
Connecting Capacity Supply Circuit |
Rigid 1 x 2.5 mm² |
Tightening Torque |
Control Circuit 0.5 N·mMain Circuit 9 N·mSupply Circuit 0.5 N·m |
Product Main Type |
PSE72 |
Function |
Soft start with torque controlSoft start with voltage rampSoft stop with torque controlSoft stop with voltage rampKick startSequence startCurrent limitStart reverse (external contactors)Automatic restartEvent log |
Protection Function |
Electronic overload protection, EOL; Locked rotor protection; Current underload protection |