Skip to content

1SDA068092R1 - XT4N 250 TMA 250-2500 3p F F

by ABB
Original price $387.25 - Original price $387.25
Original price
$387.25
$387.25 - $387.25
Current price $387.25

C.BREAKER TMAX XT4N 250 FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 250 I3=1250...2500 A



ABB EcoSolutions
Item Value
ABB EcoSolutions Yes

Circular Value
Item Value
Circular Design Principles Recyclability Rate Design for Closing Resource Loops - Standard EN45555 - 58.5 %
Conflict Minerals Reporting Template (CMRT) 9AKK108467A5658
End of Life Instructions 9AKK108468A2351
Group Waste to Landfill Target UL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA 9AKK108467A8326

Eco Transparency
Item Value
Environmental Product Declaration - EPD 9AKK108468A1892

Environmental
Item Value
Environmental Information 9AKK107991A8215 9AKK108467A6707
REACH Declaration 9AKK108466A1425
RoHS Information 9AKK108466A1424
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP 38e6bbd3-f6a2-4bae-953c-df2cb6f51486 Italy (IT)
Simplified SCIP 7d9e2a35-12f2-4631-9056-4f8d563fb73b Netherlands (NL)869abbee-8298-405e-99b7-f8136540a90e Germany (DE)ada23c35-a386-495e-9c5e-5518b5b5439c Sweden (SE)a8f1f742-49e1-4636-a082-f8d88b2828f4 Denmark (DK)60bdc153-558b-4254-bcb3-df5a272720f3 Germany (DE)558543de-ab60-40fc-a179-3afa41ca58a9 Poland (PL)0809ba82-3d29-43c1-be69-7f48153a1e5f Norway (NO)f1024a44-a324-4f63-a15b-db263d19fe6a Finland (FI)e2982b7c-b232-4fe6-abba-f159359e8ba4 Netherlands (NL)166b506a-0465-464b-a40f-e2e407667ff8 Croatia (HR)be83126a-40de-4a94-a991-83484ae53588 Czech Republic (CZ)ed3aaa4e-f7ed-4ff5-9091-5b9bbf64baff Poland (PL)e31aa327-8751-4220-acf8-ac2ad2dce84f Netherlands (NL)06015e66-7c59-4494-87f8-823390710a41 Estonia (EE)7f23468b-ed2d-4492-8884-4cb7e517ff35 Greece (GR)bb961d53-be35-4a85-a28a-0f094663aa25 Portugal (PT)2ad8ee10-39fd-43c8-97e9-21ddc85c68b1 Bulgaria (BG)f706cd52-7cec-47a5-8c17-2d234dc42e12 Sweden (SE)37ca9589-c1dd-4b56-a346-05bd14e3d7ec Poland (PL)13a61ffb-ee56-4476-b282-b9b55b0b4e02 France (FR)1b81910e-4ffe-4f91-afdc-4cad62210fbe Germany (DE)1de3d507-9595-474b-a1c4-bf68d8021cf2 Germany (DE)f9d6fac9-e0fb-4bf4-ae31-b57c219ae214 France (FR)d6228547-f0c9-4de2-a7df-0e30481009f7 Netherlands (NL)4394969b-7d81-47f8-b5d6-f892ff9a0635 Spain (ES)02cd8281-7560-410c-acae-070a9dbc1bb9 Netherlands (NL)

Ordering
Item Value
Order Code US and Canada XT4NE3250BFF000XXX
E-Number (Finland) 3638621
Minimum Order Quantity 1 piece
Customs Tariff Number 85362090

Dimensions
Item Value
Product Net Width 105 mm
Product Net Height 160 mm
Product Net Depth / Length 82.5 mm
Product Net Weight 2.252 kg

Additional Information
Item Value
Circuit Breaker Type to be Associated Power Distribution
Connecting Capacity Main Circuit Busbar 85..200 mm²
Current Type AC/DC
Electrical Durability 120 cycles per hour8000 cycle
Mechanical Durability 240 cycles per hour25000 cycle
Number of Poles 3
Opening Time CB with SOR 15 msCB with UVR 15 ms
Order Multiple 1 piece
Power Loss at Rated Operating Conditions per Pole 16.44 W
Product Main Type SACE Tmax XT
Product Name Moulded Case Circuit Breaker
Product Type Automatic Circuit Breaker
Rated Current (In) 250 A
Rated Frequency (f) 50 / 60 Hz
Rated Voltage (Ur) 690 V
Rated Impulse Withstand Voltage (Uimp) 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii) 1250…2500 A
Rated Insulation Voltage (Ui) 1000 V
Rated Operational Voltage 690 V AC750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics) (220 V AC) 65 kA(230 V AC) 65 kA(240 V AC) 65 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 36 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 10 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu) (220 V AC) 65 kA(230 V AC) 65 kA(240 V AC) 65 kA(380 V AC) 36 kA(415 V AC) 36 kA(440 V AC) 36 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 10 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu) 250 A
Recommended Screw Driver Main Circuit M8
Release TMA
Release Type TM
RoHS Date NA
Setting Range 175...250 A
Short-Circuit Performance Level N
Standards IEC
Sub-type XT4
Terminal Connection Type Front
Terminal Type Bolt
Tightening Torque 8 N·m
Version F
CAD Dimensional Drawing 1SDH002230A1003

Classifications
Item Value
ETIM 9 EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code Q
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
eClass V11.1 : 27370409

No Links Available.