Skip to content

1SFL527102R1211 - AF205-40-11-12 Contactor

by ABB
Original price $1,340.57 - Original price $1,340.57
Original price
$1,340.57
$1,340.57 - $1,340.57
Current price $1,340.57

The AF205-40-11-12 is a 4 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 110 kW / 400 V AC (AC-3) / and switching power circuits up to 350 A (AC-1) or 250 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.



Ordering
Item Value
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900

Dimensions
Item Value
Product Net Width 140 mm
Product Net Depth / Length 152.5 mm
Product Net Height 195.6 mm
Product Net Weight 3.3 kg

Technical
Item Value
Number of Main Contacts NO 4
Number of Main Contacts NC 0
Number of Auxiliary Contacts NO 1
Number of Auxiliary Contacts NC 1
Rated Operational Voltage Main Circuit 1000 V
Rated Frequency (f) Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith) acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 350 A
Rated Operational Current AC-1 (Ie) (1000 V) 40 °C 275 A(1000 V) 60 °C 250 A(1000 V) 70 °C 200 A(690 V) 40 °C 350 A(690 V) 60 °C 300 A(690 V) 70 °C 240 A
Rated Operational Current AC-3 (Ie) (415 V) 55 °C 205 A(440 V) 55 °C 205 A(380 / 400 V) 55 °C 205 A(220 / 230 / 240 V) 55 °C 205
Rated Operational Power AC-3 (Pe) (415 V) 110 kW(440 V) 132 kW(380 / 400 V) 110 kW(220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-3 8 x Ie AC-3
Rated Making Capacity AC-3 10 x Ie AC-3
Short-Circuit Protective Devices gG Type Fuses 400 A
Rated Short-time Withstand Current Low Voltage (Icw) at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1640 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 350 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 670 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2050 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 947 A
Maximum Breaking Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 A
Maximum Electrical Switching Frequency (AC-1) 300 cycles per hour
Rated Insulation Voltage (Ui) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp) Main Circuit 8 kV
Mechanical Durability 5 million
Maximum Mechanical Switching Frequency 300 cycles per hour
Coil Operating Limits (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc) 50 Hz 48 ... 130 V60 Hz 48 ... 130 VDC Operation 48 ... 130 V
Coil Consumption Holding at Max. Rated Control Circuit Voltage 50 Hz 4 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 4 V·AHolding at Max. Rated Control Circuit Voltage DC 2.5 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·APull-in at Max. Rated Control Circuit Voltage DC 150 W
Operate Time Between Coil De-energization and NO Contact Opening 45 ... 80 msBetween Coil Energization and NO Contact Closing 25 ... 60 ms
Connecting Capacity Main Circuit Flexible 1 x 6 ... 120 mm²Rigid Cu-Cable 2 x 50 ... 120 mm²
Connecting Capacity Auxiliary Circuit Flexible with Ferrule 2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type Main Circuit: Bars

Technical UL/CSA
Item Value
Maximum Operating Voltage UL/CSA Main Circuit 1000 V
General Use Rating UL/CSA (600 V AC) 250 A
Horsepower Rating UL/CSA (200 ... 208 V AC) Three Phase 30 Hp(200 V AC) Three Phase 60 hp(208 V AC) Three Phase 60 hp(220 ... 240 V AC) Three Phase 30 Hp(220 ... 240 V AC) Three Phase 75 hp(440 ... 480 V AC) Three Phase 75 Hp(440 ... 480 V AC) Three Phase 150 hp(550 ... 600 V AC) Three Phase 100 Hp(550 ... 600 V AC) Three Phase 200 hp

Environmental
Item Value
Ambient Air Temperature Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible Without Derating 3000 m
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Circular Value
Item Value
ABB EcoSolutions Yes
Circular Design Principles Recyclability Rate Design for Closing Resource Loops - Standard EN45555 - 79.2 %
End of Life Instructions 1SFC100112M0001
Group Waste to Landfill Target Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
Improved Resource Efficiency for Customers Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Sustainable Material Content Recycled Metal - 35 %

Eco Transparency
Item Value
Environmental Product Declaration - EPD 1SFC100095D0201

Classifications
Item Value
Object Classification Code Q
ETIM 4 EC000066 - Magnet contactor, AC-switching
ETIM 5 EC000066 - Magnet contactor, AC-switching
eClass V11.0 : 27371003
IDEA Granular Category Code (IGCC) 4758 >> Iec Contactors
E-Number (Finland) 3707199
E-Number (Norway) 3210330
E-Number (Sweden) 3210330

No Links Available.