Skip to content

1SDA067860R1 - XT2H 160 Ekip LS/I In=100A 3p F F

by ABB
Original price $517.42 - Original price $517.42
Original price
$517.42
$517.42 - $517.42
Current price $517.42

C.BREAKER TMAX XT2H 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP-LS/I R 100 A



ABB EcoSolutions
Item Value
ABB EcoSolutions Yes

Circular Value
Item Value
Circular Design Principles Recyclability Rate Design for Closing Resource Loops - Standard EN45555 - 58.1 %
Conflict Minerals Reporting Template (CMRT) 9AKK108467A5658
End of Life Instructions 9AKK108468A2349
Group Waste to Landfill Target UL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA 9AKK108467A8326

Eco Transparency
Item Value
Environmental Product Declaration - EPD 9AKK108468A1897

Environmental
Item Value
Environmental Information 9AKK107991A8215 9AKK108467A6707
REACH Declaration 9AKK108466A1425
RoHS Information 9AKK108466A1424
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Ordering
Item Value
Order Code US and Canada XT2HE3100EFF000XXX
Minimum Order Quantity 1 piece
Customs Tariff Number 85362090

Dimensions
Item Value
Product Net Width 90 mm
Product Net Height 130 mm
Product Net Depth / Length 82.5 mm
Product Net Weight 1.4 kg

Additional Information
Item Value
Circuit Breaker Type to be Associated Power Distribution
Connecting Capacity Main Circuit Busbar 32.5..100 mm²
Current Type AC
Electrical Durability 120 cycles per hour8000 cycle
Mechanical Durability 240 cycles per hour25000 cycle
Number of Poles 3
Opening Time CB with SOR 15 msCB with UVR 15 ms
Order Multiple 1 piece
Power Loss at Rated Operating Conditions per Pole 4.2 W
Product Main Type SACE Tmax XT
Product Name Moulded Case Circuit Breaker
Product Type Automatic Circuit Breaker
Rated Current (In) 100 A
Rated Frequency (f) 50 / 60 Hz
Rated Voltage (Ur) 690 V
Rated Impulse Withstand Voltage (Uimp) 8 kV
Rated Insulation Voltage (Ui) 1000 V
Rated Operational Voltage 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics) (220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu) (220 V AC) 100 kA(230 V AC) 100 kA(240 V AC) 100 kA(380 V AC) 70 kA(415 V AC) 70 kA(440 V AC) 65 kA(500 V AC) 50 kA(525 V AC) 30 kA(690 V AC) 15 kA
Rated Uninterrupted Current (Iu) 160 A
Recommended Screw Driver Main Circuit M6
Release Ekip LS/I
Release Type EL
Short-Circuit Performance Level H
Standards IEC
Sub-type XT2
Terminal Connection Type Front
Terminal Type Bolt
Tightening Torque 6 N·m
Version F
CAD Dimensional Drawing 1SDH002230A1001

Classifications
Item Value
ETIM 9 EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code Q
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
eClass V11.1 : 27370409

No Links Available.