NF contactor relays are used for switching auxiliary and control circuits. NF contactor relays include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...500 V 50/60 Hz or 20...500 V DC. NF contactor relays can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change. NF contactor relays have built-in surge protection and do not require additional surge suppressors. - Poles: 4-pole contactor relays - Control Circuit: AC or DC operated - Accessories: a wide range of Accessories is available. Note: NF..E-11 not suitable for a direct control by PLC-output. NF..E-11 type available in some countries: please consult your ABB representative.
Technical
Item |
Value |
Number of Auxiliary Contacts NO |
4 |
Number of Auxiliary Contacts NC |
0 |
Standards |
IEC/EN 60947-1, IEC/EN 60947-5-1, UL 508, CSA C22.2 No. 14-13 |
Rated Operational Voltage |
Auxiliary Circuit 690 V |
Rated Frequency (f) |
Auxiliary Circuit 50 / 60 HzControl Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith) |
acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
Rated Operational Current AC-15 (Ie) |
(500 V) 2 A(690 V) 2 A(24 / 127 V) 6 A(220 / 240 V) 4 A(400 / 440 V) 3 A |
Rated Short-time Withstand Current Low Voltage (Icw) |
for 0.1 s 140 Afor 1 s 100 A |
Maximum Electrical Switching Frequency |
(AC-15) 1200 cycles per hour(DC-13) 900 cycles per hour |
Rated Operational Current DC-13 (Ie) |
(24 V) 6 A / 144 W(48 V) 2.8 A / 134 W(72 V) 1 A / 72 W(110 V) 0.55 A / 60 W(125 V) 0.55 A / 69 W(220 V) 0.27 A / 60 W(250 V) 0.27 A / 68 W(400 V) 0.15 A / 60 W(500 V) 0.13 A / 65 W(600 V) 0.1 A / 60 W |
Rated Insulation Voltage (Ui) |
acc. to IEC 60947-5-1 690 Vacc. to UL/CSA 600 V |
Rated Impulse Withstand Voltage (Uimp) |
6 kV |
Maximum Mechanical Switching Frequency |
6000 cycles per hour |
Rated Control Circuit Voltage (Uc) |
50 Hz 24 ... 60 V60 Hz 24 ... 60 VDC Operation 20 ... 60 V |
Operate Time |
Between Coil De-energization and NC Contact Closing 13 ... 98 msBetween Coil De-energization and NO Contact Opening 11 ... 95 msBetween Coil Energization and NC Contact Opening 38 ... 90 msBetween Coil Energization and NO Contact Closing 40 ... 95 ms |
Mounting on DIN Rail |
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting by Screws (not supplied) |
2 x M4 screws placed diagonally |
Connecting Capacity Auxiliary Circuit |
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm² |
Connecting Capacity Control Circuit |
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²Rigid Solid 1/2x 1 ... 2.5 mm²Rigid Stranded 1/2x 1 ... 2.5 mm² |
Wire Stripping Length |
Auxiliary Circuit 10 mmControl Circuit 10 mm |
Degree of Protection |
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
Terminal Type |
Screw Terminals |
Environmental
Item |
Value |
Ambient Air Temperature |
Close to Contactor for Storage -60 ... +80 °CNear Contactor for Operation in Free Air -40 ... 70 °C |
Climatic Withstand |
Category B according to IEC 60947-1 Annex Q |
Maximum Operating Altitude Permissible |
Without Derating 3000 m |
Resistance to Vibrations acc. to IEC 60068-2-6 |
5 ... 300 Hz 4 g closed position / 2 g open position |
Resistance to Shock acc. to IEC 60068-2-27 |
Closed, Shock Direction: B1 25 gOpen, Shock Direction: B1 5 gShock Direction: A 30 gShock Direction: B2 15 gShock Direction: C1 25 gShock Direction: C2 25 g |
RoHS Status |
Following EU Directive 2011/65/EU |