Skip to content

1SDA068229R1 - XT3S 250 TMD 125-1250 4p F F InN=100%

by ABB
Original price $478.85 - Original price $478.85
Original price
$478.85
$478.85 - $478.85
Current price $478.85

C.BREAKER TMAX XT3S 250 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 125-1250 A FULLY RATED NEUTRAL



ABB EcoSolutions
Item Value
ABB EcoSolutions Yes

Circular Value
Item Value
Circular Design Principles Recyclability Rate Design for Closing Resource Loops - Standard EN45555 - 60.5 %
Conflict Minerals Reporting Template (CMRT) 9AKK108467A5658
End of Life Instructions 9AKK108468A2350
Group Waste to Landfill Target UL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA 9AKK108467A8326

Eco Transparency
Item Value
Environmental Product Declaration - EPD 9AKK108468A2294

Environmental
Item Value
Environmental Information 9AKK107991A8215 9AKK108467A6707
REACH Declaration 9AKK108466A1425
RoHS Information 9AKK108466A1424
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Ordering
Item Value
Order Code US and Canada XT3SE4125AFF000XXX
Minimum Order Quantity 1 piece
Customs Tariff Number 85362090

Dimensions
Item Value
Product Net Width 140 mm
Product Net Height 150 mm
Product Net Depth / Length 70 mm
Product Net Weight 2.1 kg

Additional Information
Item Value
Circuit Breaker Type to be Associated Power Distribution
Connecting Capacity Main Circuit Busbar 85..192 mm²
Current Type AC/DC
Electrical Durability 120 cycles per hour8000 cycle
Mechanical Durability 240 cycles per hour25000 cycle
Number of Poles 4
Opening Time CB with SOR 15 msCB with UVR 15 ms
Order Multiple 1 piece
Power Loss at Rated Operating Conditions per Pole 6.6 W
Product Main Type SACE Tmax XT
Product Name Moulded Case Circuit Breaker
Product Type Automatic Circuit Breaker
Rated Current (In) 125 A
Rated Frequency (f) 50 / 60 Hz
Rated Voltage (Ur) 690 V
Rated Impulse Withstand Voltage (Uimp) 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii) 1250 A
Rated Insulation Voltage (Ui) 800 V
Rated Operational Voltage 690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics) (220 V AC) 42.5 kA(230 V AC) 42.5 kA(240 V AC) 42.5 kA(380 V AC) 27 kA(415 V AC) 27 kA(440 V AC) 20 kA(500 V AC) 15 kA(525 V AC) 10 kA(690 V AC) 3 kA(250 V DC) 2 Poles in Series 27 kA(500 V DC) 3 Poles in Series 37.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu) (220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 40 kA(500 V AC) 30 kA(525 V AC) 20 kA(690 V AC) 6 kA(250 V DC) 2 Poles in Series 36 kA(500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu) 250 A
Recommended Screw Driver Main Circuit M8
Release TMD
Release Type TM
Setting Range 87.5...125 A
Short-Circuit Performance Level S
Standards IEC
Sub-type XT3
Terminal Connection Type Front
Terminal Type Bolt
Tightening Torque 8 N·m
Version F
CAD Dimensional Drawing 1SDH001295R0483

Classifications
Item Value
ETIM 9 EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code Q
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
eClass V11.1 : 27370409

No Links Available.