Skip to content

1SAM250000R1010 - MS116-10 Manual Motor Starter 6.3 ... 10 A

by ABB
Original price $39.32 - Original price $39.32
Original price
$39.32
$39.32 - $39.32
Current price $39.32

The MS116-10 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 10.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A.



Ordering
Item Value
Minimum Order Quantity 1 piece
Customs Tariff Number 85362010

Dimensions
Item Value
Product Net Width 45 mm
Product Net Height 90 mm
Product Net Depth / Length 85.6 mm
Product Net Weight 0.265 kg

Technical
Item Value
Rated Service Short-Circuit Breaking Capacity (Ics) (230 V AC) 50 kA(400 V AC) 50 kA(440 V AC) 6 kA(500 V AC) 6 kA(690 V AC) 2 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu) (230 V AC) 75 kA(400 V AC) 75 kA(440 V AC) 18 kA(500 V AC) 15 kA(690 V AC) 3 kA
Rated Instantaneous Short-Circuit Current Setting (Ii) 150 A
Setting Range 6.3 ... 10 A
Rated Operational Power AC-3 (Pe) (400 V) Three Phase 4 kW
Rated Operational Power AC-3e (Pe) (400 V) Three Phase 4 kW
Rated Operational Voltage Main Circuit 690 V AC
Rated Operational Current (Ie) 10 A
Rated Operational Current AC-3 (Ie) 10 A
Rated Operational Current AC-3e (Ie) 10 A
Rated Frequency (f) Main Circuit 50 HzMain Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp) Main Circuit 6 kV
Rated Insulation Voltage (Ui) 690 V
Power Loss at Rated Operating Conditions per Pole 0.9 ... 2.4 W
Number of Poles 3
Conventional Free-air Thermal Current (Ith) Main Circuit 10 A
Degree of Protection Housing IP20Main Circuit Terminals IP10
Pollution Degree 3
Electrical Durability 100000 cycle
Mechanical Durability 100000 cycle
Terminal Type Screw Terminals
Connecting Capacity Main Circuit Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²Flexible 1/2x 0.75 ... 2.5 mm²Rigid 1/2x 1 ... 4 mm²
Tightening Torque Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length Main Circuit 9 mm
Recommended Screw Driver Pozidriv 2
Mounting Position any1 ... 6
Mounting on DIN Rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance Electrical Conductive Board, Horizontal - Up to 400 V 0 mmElectrical Conductive Board, Horizontal - Up to 690 V 1.5 mmElectrical Conductive Board, Vertical 75 mmOther Device Same Type, Horizontal 0 mmOther Device Same Type, Vertical 150 mm
Actuator Type Rotary Handle
Contact Position Indication ON / OFF
Standards IEC/EN 60947-1IEC/EN 60947-2IEC/EN 60947-4-1UL 60947-1UL 60947-4-1

Technical UL/CSA
Item Value
Short-Circuit Current Rating (SCCR) Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 18 kAAny UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 5 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 18 kAAny UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 5 kA
Maximum Operating Voltage UL/CSA Main Circuit 600 V AC
Horsepower Rating UL/CSA (200 V AC) Three Phase 2 Hp(208 V AC) Three Phase 2 Hp(220 ... 240 V AC) Three Phase 3 Hp(440 ... 480 V AC) Three Phase 5 Hp(550 ... 600 V AC) Three Phase 7.5 Hp
Full Load Amps Motor Use (200 V AC) Three Phase 7.8 A(208 V AC) Three Phase 7.5 A(220 ... 240 V AC) Three Phase 9.6 A(440 ... 480 V AC) Three Phase 7.6 A(550 ... 600 V AC) Three Phase 9 A
Locked Rotor Amps (200 V AC) Three Phase 57.5 A(208 V AC) Three Phase 55 A(220 ... 240 V AC) Three Phase 64 A(440 ... 480 V AC) Three Phase 46 A(550 ... 600 V AC) Three Phase 50.8 A
General Use Rating UL/CSA (600 V AC) 10 A
Connecting Capacity Main Circuit UL/CSA Flexible 1/2x 16-12 AWGStranded 1/2x 16-12 AWG
Tightening Torque UL/CSA Main Circuit 10 in·lb

Environmental
Item Value
Ambient Air Temperature Around the Enclosure 0 ... +40 °COperation -25 ... +70 °COperation Compensated -25 ... +55 °CStorage -50 ... +80 °C
Ambient Air Temperature Compensation Yes
Maximum Operating Altitude Permissible 2000 m
Resistance to Shock acc. to IEC 60068-2-27 11 ms Pulse 25g
Resistance to Vibrations acc. to IEC 60068-2-6 5g / 3 ... 150 Hz
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Classifications
Item Value
Object Classification Code F
ETIM 4 EC000074 - Motor protective circuit-breaker
ETIM 5 EC000074 - Motor protective circuit-breaker
eClass V11.0 : 27370401
IDEA Granular Category Code (IGCC) 4731 >> Manual Starters
E-Number (Finland) 3706010
E-Number (Sweden) 3111948

No Links Available.