Skip to content

1SDA067574R1 - XT2S 160 TMD 32-320 4p F F

by ABB
Original price $356.68 - Original price $356.68
Original price
$356.68
$356.68 - $356.68
Current price $356.68

C.BREAKER TMAX XT2S 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 32-320 A



ABB EcoSolutions
Item Value
ABB EcoSolutions Yes

Circular Value
Item Value
Circular Design Principles Recyclability Rate Design for Closing Resource Loops - Standard EN45555 - 58.1 %
Conflict Minerals Reporting Template (CMRT) 9AKK108467A5658
End of Life Instructions 9AKK108468A2348
Group Waste to Landfill Target UL 2799 Zero Waste To Landfill Validation available
Toxic Substances Control Act - TSCA 9AKK108467A8326

Eco Transparency
Item Value
Environmental Product Declaration - EPD 9AKK108468A1891

Environmental
Item Value
Environmental Information 9AKK107991A8215 9AKK108467A6707
REACH Declaration 9AKK108466A1425
RoHS Information 9AKK108466A1424
RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Ordering
Item Value
Order Code US and Canada XT2SE4032AFF000XXX
Minimum Order Quantity 1 piece
Customs Tariff Number 85362090

Dimensions
Item Value
Product Net Width 120 mm
Product Net Height 130 mm
Product Net Depth / Length 82.5 mm
Product Net Weight 1.6 kg

Additional Information
Item Value
Circuit Breaker Type to be Associated Power Distribution
Connecting Capacity Main Circuit Busbar 32.5..100 mm²
Current Type AC/DC
Electrical Durability 120 cycles per hour8000 cycle
Mechanical Durability 240 cycles per hour25000 cycle
Number of Poles 4
Opening Time CB with SOR 15 msCB with UVR 15 ms
Order Multiple 1 piece
Power Loss at Rated Operating Conditions per Pole 2.57 W
Product Main Type SACE Tmax XT
Product Name Moulded Case Circuit Breaker
Product Type Automatic Circuit Breaker
Rated Current (In) 32 A
Rated Frequency (f) 50 / 60 Hz
Rated Voltage (Ur) 690 V
Rated Impulse Withstand Voltage (Uimp) 8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii) 320 A
Rated Insulation Voltage (Ui) 1000 V
Rated Operational Voltage 690 V AC500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics) (220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 36 kA(525 V AC) 25 kA(690 V AC) 12 kA(250 V DC) 2 Poles in Series 50 kA(500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu) (220 V AC) 85 kA(230 V AC) 85 kA(240 V AC) 85 kA(380 V AC) 50 kA(415 V AC) 50 kA(440 V AC) 50 kA(500 V AC) 36 kA(525 V AC) 25 kA(690 V AC) 12 kA(250 V DC) 2 Poles in Series 50 kA(500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu) 160 A
Recommended Screw Driver Main Circuit M6
Release TMD
Release Type TM
Setting Range 22.4...32 A
Short-Circuit Performance Level S
Standards IEC
Sub-type XT2
Terminal Connection Type Front
Terminal Type Bolt
Tightening Torque 6 N·m
Version F
CAD Dimensional Drawing 1SDH002230A1002

Classifications
Item Value
ETIM 9 EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code Q
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
eClass V11.1 : 27370409